Vertiv | Liebert CRV+ | User Manual 34
The refrigeration oil used in the Liebert CRV+ air conditioner is depicted in the table in Listing 2.9:
Listing 2.9
Types of refrigeration oil
CR 012 PVE (FV505)
CR025 POE (RL32H)
Table depicting the amount of refrigeration oil to be added
Refrigeration oil adding amount with different pipe length
(length unit: mm, refrigeration oil unit: ml)
pipe OD
(mm)
10 20 30 35 40 45 50
12.7
Refrigeration oil charging is not
needed
charging is not needed
15 30
pipe OD
(mm)
10 20 30 35 40 45 50
12.7
Refrigeration oil charging is not
needed
Refrigeration oil charging is not
needed
32
pipe OD
(mm)
10 20 30 35 40 45 50
16
Refrigeration oil charging is not
needed
Refrigeration oil charging is not
needed
13
22 39 55 71 87
Consult Vertiv Co. for adding the refrigeration oil
Do not use poor quality refrigeration oil as it can damage the system
Select the right make and type of refrigeration oil depending on the model.
If any error or damage occurs due to adding the incorrect make and type of oil, the warranty
will be void.
2.3.6 Removing Transportation Fastener and Vibration Absorber
Certain fasteners and vibration absorbers are mounted on the equipment to protect partial components
from getting damaged and distorted due to bumping, impact, and resonance.