Figure 2-20 depicts the connection of the bottom water inlet pipe of the electrode humidifier:
Figure 2-20 Connection of bottom water inlet pipe of electrode humidifier
Connecting the Copper pipes between the Indoor and Outdoor unit
The indoor and outdoor units are connected through welded copper pipes. Considering the effect of the
pipe diameter on the system pressure drop, the pipe diameter of the indoor unit and outdoor unit should
be determined by the specifications mentioned in the table under Listing 2.5. Alternatively, contact the
Vertiv support office to seek the help of the technician for gauging the length and diameter.
Listing 2.5
Pipe length D L D L D L
20m 16 12.7 19 16 22 19
40m* 19 16 22 16 25 19
A pipe extension kit is required for Equivalent Length marked with *.
D: Discharge line; L: Liquid Line
Consult Vertiv Co.If the pipe length exceeds 50m or 30m.
If the outdoor environment is lower than -20 °C, a low temperature kit is required. Therefore,
consult Vertiv Co. for the same.
Water inlet
soft pipe
Water inlet
hole
Top water inlet
copper pipe