Vertiv | Liebert® CRV4 | User Manual 93
System Operation and Maintenance
Figure 8-4 Interface of Humidication Control Board
8.7.2. Replacing Humidier
Due to the sediments in the water drained from the humidier, the humidier tray must be cleaned periodically
to avoid clogging of the tray and the drainage pipe. The cleaning cycle varies with the water quality, as well
as the humidication operation time. Timely cleaning of the humidier tray must be done every month, as a
consumable, the humidier doesn’t require regular cleaning. If the water keeps entering the humidier or the
input voltage of the humidication electrode is normal, but the water fails to boil, it means that the humidier
has reached its service life and needs replacement.
Following are the procedures to replace the humidier:
1. Turn O the humidier by setting the humidity setpoints on the controller lower than the actual humidity in
the equipment room.
2. Place the RUN/ DRAIN switch to the DRAIN position to forcefully empty the humidier.
3. Turn O the AC power.