Vertiv | Liebert® CRV4 | User Manual 7
Installation
2.2. Installation Space Requirements
The Liebert® CRV4 unit is a set of full-featured air-cooled direct expansion type row-cooling unit. It is
recommended to install the unit with a row of high heat density server cabinets in an alternative manner, to form
a hot aisle and cold aisle conguration.
2.2.1. Maintenance Space Requirements for Liebert CRV4
In normal condition, a provision space of 600 mm in the front and rear sides should be reserved for maintenance
activities. Refer Figure 2-1 for better understanding and Table 2-1 describes the requirements for minimum
maintenance space as per the models
Figure 2-1 Space Clearance for Maintenance (unit: mm)
Table 2-1 Minimum Clearance Space for Maintenance
Location
CR025 CR035
CR045
mm inch mm inch
mm inch
Front 600 23.6 600 23.6
600 23.6
Rear 600 23.6 600 23.6
600 23.6
The space is used for regular maintenance, such as replacing lter, fan, electrode humidier and so on. In case
of special application Contact Vertiv representative.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert CRV4 Series and is the answer not in the manual?

Vertiv Liebert CRV4 Series Specifications

General IconGeneral
BrandVertiv
ModelLiebert CRV4 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals