3.3.1 Expansion Tank
The expansion tank, included in a standard pump package, has an internal volume of 8.8gal.(33l) and a maximum pressure
of 100psi(690kPa).
The tank is sized for a typical “open” system with a fluid volume of less than 75gal.(280l). When used in a “closed” system,
volumes of up to 140gal.(530l) can be accommodated. We recommend use of a field-supplied safety-relief valve for
systems “closed” to atmospheric venting. Other piping accessories for filling, venting, or adjusting the fluid in the system,
are recommended, but not included.
The planning dimensions and general arrangement are described in the submittal documents included in the Submittal
Drawings Contents on page65.
The following table lists the relevant documents by number and title.
Document Number Title
DPN004183 Expansion Tank General Arrangement and Dimensional Data
Table 3.5 Drycooler Pump and Tank Drawings
3.3.2 Compression Tank
The compression tank for glycol/GLYCOOL™ systems includes:
• Tank
• Airtrol fitting
• Sight glass with shut-off valves
• 50-psi relief valve
• Drain valve
Mounting brackets are not included. Maximum design pressure 125psig.
The planning dimensions and general arrangement are described in the submittal documents included in the Submittal
Drawings Contents on page65.
The following table lists the relevant documents by number and title.
Document Number Title
DPN003898 Compression Tank General Arrangement and Dimensional Data
Table 3.6 Drycooler Pump and Tank Drawings