ASME COMPRESSION TANK KITS GLYCOL/GLYCOOLâ„¢ SYSTEMS
Form No.: DPN001040_REV4
GENERAL ARRANGEMENT DIAGRAM & DIMENSIONAL DATA
LIEBERT DRYCOOLER
(GAL) (GAL) A B C D
(NPT Female)
(NPT Female)
Lbs. (kg)
250 15 34-1/8 (867) 19 (483) 60 (27.2)
400 24 52-1/8 (1324) 37 (940) 75 (34.0)
500 30 49-3/8 (1254) 31-1/4 (794) 82 (37.2)
650 40 64-3/8 (1635) 46-1/4 (1175) 105 (47.6)
1000 60 16 (406) 73 (1854) 53-1/2 (1359) 12 (305) 140 (63.5)
1650 100 20 (508) 80-5/16 (2040) 58 (1473) 16 (406) 200 (90.7)
DIMENSIONS in. (mm)
TANK
CAPACITY
MAXIMUM
SYSTEM
APPROX. KIT
WT.
1" 1/2"
12 (305)
14 (356)
8 (203)
10 (254)
Shutoff Valve
Pitch minimum 1" per foot
Gauge Glass w/
Shutoff Valves
Compression Tank
Drain
Glycol loop piping
Air Tube
Pressure Relief Valve
To Suction side
of Pump
W
D
C
A
T
Drain Tank
Fitting
Airtrol Tank Fitting
(Combination Air Vent
& Liquid Control)
1
1
1
1
2
Notes:
1. These components are factory supplied and shipped loose.
Field installtion and piping by others.
2. These components are not factory supplied by Liebert, but are
required for proper system operation and maintenance. Field
installation and piping by others.
3. Field to provide a means for adding pre-mixed Glycol to system.
4. Install compression tank at the highest point of the system.