EasyManua.ls Logo

Vertiv Liebert Mini-Mate2 - Optional Equipment Piping; Free-Cooling Coil; Hot Water Reheat Coil

Vertiv Liebert Mini-Mate2
92 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.8 Optional Equipment Piping
7.8.1 Free-Cooling Coil
The free-cooling coil is a secondary coil located downstream of the DX coil. The free-coiling coil does not
operate at the same time as the DX coil. A temperature sensor is factory-mounted to the free-cooling
piping. If the water temperature is less than the set temperature (usually 45°F [7.2°C]), the 3-way valve
opens to allow chilled water flow to the free-cooling coil and the compressor is locked off. If the water
temperature is above the set temperature, the 3-way valve closes (bypasses) and enables the compressor.
To keep deposits from building up in the free-cooling coil, an adjustable timer is factory-set to flush every
400 minutes.
NOTE: If the free-cooling coil is piped to an open water tower, a CU/NI (copper-nickel) type coil must
be ordered to prevent corrosion of the copper tubes; or a heat exchanger must separate the tower
water from the free-cooling loop.
On water-cooled systems, the free-cooling coil outlet can be field piped to the condensing unit inlet,
provided a 3-way regulating valve has been installed within the water/glycol condensing unit (see Figure
7.17 below).
Figure 7.17 Optional free-cooling coil (3-way valve) on water/glycol units
7.8.2 Hot Water Reheat Coil
Building hot water can be piped to a factory-installed hot water reheat coil, located downstream of the
cooling coil. A factory-installed solenoid valve opens upon a call for reheat.
Vertiv | Liebert Mini-Mate25 ton User Manual| 52

Table of Contents

Related product manuals