22
Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
WARNING: Before any calibration with the unit
operating, remove the call for humidication and
electrical heating at the control.
9.1 - Water leakage sensor (Liquistat)
Due to high ooding alarm device sensitivity, to the end to avoid
undesirable alarm signal because of few sporadic water drops,
place the sensors at a minimum distance of 500 mm from the unit
base perimeter.
This solution assures alarm intervention for real ooding risk only.
9.2 - Environment protection
A misuse or an incorrect calibration of the unit leads to an increased
energy consumption, resulting in an economic and environmental
damage. Use the freecooling function, if available.