Vertiv Liebert PDX - Floor Hole Requirements for Downflow Units

Vertiv Liebert PDX
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Enclosure C - Installation drawings
C - 2Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
Fig. 2 Hole in the oor for Downow versions
Downow Up
Downow Down
Tab. 2 - Hole in the oor for Downow units, dimensions in mm
C o n g u r a t i o n Unit PX082 PX094 PX104 PX120
PX150
PX165
Downow Up
A 2450 3250
B 760 760
C* 70 70
With Base Frame **
A 2526 3326
B 840 840
C* 30 30
With Legs kit **
A 2506 3306
B 820 820
C* 30 30
Downow Down
A 2532 3332
B 846 846
C* 20 20
With oor tiles support kit **
A 2570 3370
B 885 885
C* 50 50
* Minimal distance of the working unit from the back wall. Caution: In order to assemble and/or install accessories, a larger distance might be required. In that case, the unit can be moved in the
working position after installation / assembly procedures.
** Optional accessories - see details in Enclosures E.