Enclosure B - Technical data table
B - 2Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
Component
COMPRESSOR
(400V / 3Ph / 50Hz)
Model
OA** [A] FLA [A] LRA [A]
Nominal power**
[kW]
Winding resistance
(Ohm)
Digital
Scroll
version with
premium fan
module
PX082 16.56+16.5 2x15+2x15 2x75+2x75 9.35+9.29 (2.26+2.27)+(2.26+2.27)
PX094 15+14.90 2x15+2x15 2x101+2x101 10.68+10.64 (1.79+1.79)+(1.79+1.79)
PX104 21.76+21.85 2x16.20+2x16.2 2x101+2x101 11.2+11.22 (1.79+1.79)+(1.79+1.79)
PX120 28.14+24.76 2x22+2x21 2x118+2x111 14.82+12.72 (1.23+1.24)+(1.47+1.36)
PX150 36,63+30,77 2x31+2x25 2x140+2x118 19,53+16,77 (1,11+1,11)+(1,23+1,24)
PX165 35.89+45.38 2x34+2x31 2x174+2x140 19.08+22.89 (0,83+0,83)+(1,11+1,11)
(*) At standard operating conditions, Filters class F5, ESP: Downow Up 20 Pa; Downow Frontal 0 Pa.
(**)At nominal operating conditions: Condensing temperature 45
0
C - Room conditions 36
0
C / 24% RH
Tab. 4 - Electrical data (optional components)
COMPONENT
Model
ELECTRICAL HEATING ELECTRODE HUMIDIFIER CONDENSATE PUMP
Std. Capacity Opt. High Capacity
FLA [A]
Nominal power
[kW]
FLA [A]
Nominal power
[kW]
FLA
[A]
Nominal power
[kW]
FLA
[A]
Nominal power
[kW]
(400V / 3Ph / 50Hz)
PX082
10.8 7.5
32.5 22.5
13.0 9.0 1.6 0.15
PX094 32.5 22.5
PX104 32.5 22.5
PX120 32.5 22.5
PX150 32.5 22.5
PX165 32.5 22.5

Table of Contents