58 Operating manual Voltwerk VS 3, 4, 5
8 Help in the case of faults
ENGLISH
DO_BA_2008_121LB_3ENG_BVo 22.2.10
8.2 Messages in the display
If a fault occurs in the inverter, the current fault indicator will
be shown in the display. The top line shows the numeric code
of the fault, and the second line gives a fault indicator. The
faults listed cause the inverter to switch off. It normally
switches back on automatically once the fault has been
cleared. If the inverter does not switch back on or you cannot
clear the fault, contact the manufacturer's service centre
(contact information on the back of the manual).
LED is off
The status of this LED indicator has no signifi-
cance for the information currently displayed.
Fault indicator Possible cause Possible fault rectification
TEMP HIGH | Ambient temperature is
too high
The inverter requires cool ambi-
ent air
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
| Test the fans (see chapter 7.2,
page 47)
TEMP LOW | Ambient temperature is
too low,
T < -20 °C
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
TEMP CRITICAL | Temperature in the de-
vice is too high
| Electronics fault
|Fan fault
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
| Test the fan (see chapter 7.2,
page 47)
| If the fault continues, contact
the manufacturer's service
centre (contact information on
the back of the manual).