What does loop reversed error mean on my Watlow F4T?
- JJoseph HallSep 13, 2025
A loop reversed error on your Watlow Controller may occur due to: * An incorrect setting of the Open Loop Detect Time. Set the correct Open Loop Detect Time for the application. * An incorrect setting of the Open Loop Detect Deviation. Set the correct Open Loop Deviation value for the application. * An output programmed for an incorrect function. Set the output function correctly. * A thermocouple sensor wired in reverse polarity. Wire the thermocouple correctly (red wire is negative).