Watlow F4T Install & Troubleshooting 11 Chapter 2 Install and Wire
Place the Quencharc directly across the external coil as shown below. For a DC load, place
the cathode of the diode, to the positive voltage of the load and the anode to the ground of
the load.
Note:
It is possible that the terminal strip labeling for any given module could be the same. For
example, if a Thermocouple input module is installed in slot 1 and 2, each slot would have
S1 and R1 on its label. When referencing either of these inputs the differentiating factor is
the module slot number, therefore the reference should be input 1 of slot number x.
Note:
Maintain electrical isolation between the analog input, digital input-outputs, switched dc/
open collector outputs and process outputs to prevent ground loops.
Note:
The F4T meets IP10 requirements when the empty slots have slot caps installed.
Note:
Maximum wire size and torque for screw terminations:
0.0507 to 3.30 mm2 (30 to 12 AWG) single-wire termination or two 1.31 mm2 (16 AWG)
0.57 Nm (5.0 lb.-in.) torque
Input Connections
Thermocouple FM [M, L] A - [L, U, Y] _ _ A - A _ _ _
S1
R1
Grounded or ungrounded sensors, greater than 20MΩ input imped-
ance, 2kΩ source resistance max.
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The negative lead (usually red)
must be connected to S terminal
To reduce errors, the extension wire for thermocouples must be of the
same alloy as the thermocouple.
Thermocouple (High Density) FMHA - RAAA - A _ _ _
-
+
-
+
-
+
-
+
S1
R1
S2
R2
S3
R3
S4
R4
Grounded or ungrounded sensors, greater than 20MΩ input imped-
ance, 2kΩ source resistance max
3 microampere open-sensor detection
Thermocouples are polarity sensitive. The negative lead (usually
red) must be connected to S terminal
To reduce errors, the extension wire for thermocouples must be of
the same alloy as the thermocouple
Quencharc
Watlow Part #: 0804-0147-0000
User Load
L
_
K
_
N
Anderson-Bolds ~ 216-360-9800
www.anderson-bolds.com

Other manuals for Watlow F4T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watlow F4T and is the answer not in the manual?

Watlow F4T Specifications

General IconGeneral
InputsThermocouple, RTD, mA, V
OutputsRelay, SSR, mA, V
CommunicationEthernet, Modbus RTU
Data LoggingYes
CertificationsCE, UL, cUL, RoHS
Control ModesPID, On/Off
Power Supply100 to 240 VAC
Operating Temperature0 to 50°C
Enclosure RatingIP65
Display4.3 in. (109 mm) color touch panel LCD
Control LoopsUp to 4