3.3.2 Standard Definitions
IEC/EN 61800-3: “Adjustable Speed Electrical Power Drives Systems”
Environment:
First Environment: includes domestic premises. It also includes establishments directly connected without
intermediate transformer to a low-voltage power supply network which supplies buildings used for domestic
purposes.
Exemplo: houses, apartments, commercial installations, or offices located in residential buildings.
Second Environment: includes all establishments other than those directly connected to a low-voltage power
supply network which supplies buildings used for domestic purposes.
Example: industrial area, technical area of any building supplied by a dedicated transformer.
Categories:
Category C1: converters with a voltage rating less than 1000 V and intended for use in the First Environment.
Category C2: converters with a voltage rating less than 1000 V, intended for use in the First Environment, not
provided with a plug connector or a movable installations, and installed and commissioned by a professional.
Note: a professional is a person or organization familiar with the installation and/or commissioning of converters,
including the EMC aspects.
Category C3: converters with a voltage rating less than 1000 V and intended for use in the Second Environment
only (not designed for use in the First Environment).
Category C4: converters with a voltage rating equal to or greater than 1000 V, or with a current rating
equal to or greater than 400 Amps, or intended for use in complex systems in the Second Environment.
EN 55011: “Threshold values and measuring methods for radio interference from industrial, scientific
and medical (ISM) high-frequency equipment”.
Class B: equipment intended for use in the low-voltage power supply network (residential, commercial, and light-
industrial environments).
Class A1: equipment intended for use in the low-voltage power supply network. Restricted distribution.
Nota: quando forem usados em redes públicas deverão ser instalados e colocados em funcionamento por
profissional.
Class A2: equipment intended for use in industrial environments.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the WEG CFW-11 RB and is the answer not in the manual?

WEG CFW-11 RB Specifications

General IconGeneral
BrandWEG
ModelCFW-11 RB
CategoryMedia Converter
LanguageEnglish