DETAILED PARAMETER DESCRIPTION
Table 5.33: JOG Selection - REMOTE Situation
P0228 Function
0
Disable
1
HMI
key
2
Digital inputs DI3 to DI10 (P0265 to P0272)
3
Serial
4
Fieldbus
5
PLC
6
Graphic HMI
key
✓
NOTE!
This parameter can be changed only with the motor stopped.
P0231 - Actuation in the transition between Local and Remote for the HMIG
Adjustable range: 0 to 2 Factory setting: 0
Acesso: Menu → Configurations → Commands → Local
Description:
P0231 defines the action to be taken by the inverter when the transition between LOCAL and REMOTE occurs
for the Graphic HMI.
This parameter only actuates when P0224 = 5 (Graphic HMI
and
key) or P0227 = 5 (Graphic HMI
and
key).
(*) In case the motor stops, it occurs according to the programming of P0232 (Stop Selection).
Table 5.34: Actuation in the transition between Local and Remote for the HMIG
P0231 Function
0
It keeps the motor state
1
It keeps the HMI state
2
It turns off the motor
P0232 - Stop Selection
Adjustable range: 0 to 1 Factory setting: 0
Acesso: Menu → Configurations → Commands → Local
Description:
With the P0232 setting, it is possible to select between the stop modes (Run/Stop and General disable) for
the
key or for the STOP function (via DIx).
✓
NOTE!
When the “DISABLE GENERAL” stop mode is programmed, only drive the motor if it is stopped or
set the necessary time for which the inverter is disabled (COAST) in P0725 to ensure the motor stop,
or enable the Flystart function.
Table 5.35: Stop Selection
P0232 Function
0
Run/Stop
1
General disable
MVW3000 | 5-43