QUICK REFERENCE OF PARAMETERS AND FAULTS
Param. Description Adjustable range Factory
setting
Page
P0295
(1)
Inverter rated current 0 = 24 A
1 = 40 A
2 = 50 A
3 = 60 A
4 = 70 A
5 = 80 A
6 = 90 A
7 = 100 A
8 = 110 A
9 = 125 A
10 = 140 A
11 = 160 A
12 = 180 A
13 = 200 A
14 = 225 A
15 = 265 A
16 = 310 A
17 = 340 A
18 = 400 A
19 = 450 A
20 = 500 A
21 = 550 A
22 = 600 A
23 = 650 A
24 = 700 A
25 = 750 A
26 = 800 A
27 = 850 A
28 = 900 A
10 5-65
P0296
(7)
Inverter rated voltage 0 = 1150 V
1 = 2300 V
2 = 3300 V
3 = 4160 V
4 = 5500 V
5 = 6300 V
6 = 6900 V
7 = 7200 V
8 = 8000 V
9 = 9000 V
10 = 10000 V
11 = 11000 V
12 = 12000 V
13 = 13200 V
14 = 13800 V
14 5-66
P0303 Skipped Speed 1 0 to 4095 rpm 600 rpm 5-66
P0304 Skipped Speed 2 0 to 4095 rpm 900 rpm 5-66
P0305 Skipped Speed 3 0 to 4095 rpm 1200 rpm 5-66
P0306 Skipped Range 0 to 750 rpm 0 rpm 5-66
P0308
(1)
Serial address 1 to 30 1 5-67
P0309
(1)
Fieldbus 0 = Inactive
1 = Profibus-DP 2 I/O
2 = Profibus-DP 4 I/O
3 = Profibus-DP 6 I/O
4 = DeviceNet 2 I/O
5 = DeviceNet 4 I/O
6 = DeviceNet 6 I/O
7 = Modbus-RTU 2 I/O
8 = Modbus-RTU 4 I/O
9 = Modbus-RTU 6 I/O
10 = DeviceNet Drive Profile
11 = Ethernet 2 I/O
12 = Ethernet 4 I/O
13 = Ethernet 6 I/O
0 5-67
MVW3000 | 1-18