Westerbeke 12.5 BTDA - Generator Frequency Adjustment Steps; AC Voltage Connections (6 & 12 Stud)

Westerbeke 12.5 BTDA
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GENERATOR
VOLTAG~
ADJUSTMENT
NOTE:.
WESTERBEKE
recommends
that
the
following
generator
tests
and
adjustments
be
performed
by
a
quailijied
technician.
Generator
Frequency
I.
Frequency
is
a
direct
result of
engine/generator
speed:
1800
rpm =
60
hertz
1500
rpm
=
50
hertz.
2.
To
change
generator
frequency
follow
the
sfeps
below.
a.
Connect
the
AC
output
leads
to
the
AC
tel111ina1
block,
following
the
illustrations
on
this
page.
b.
If
an
AVR
is
installed,
reposition
the blue or
blue/white
lead
to
correspond
to
the
hertz
selected
on
the
Voltage/Hertz
Connection
Bar.
If
there
is
no automatic voltage regulator
(AVR
installed, do not change the wiring
on
the
Voltage/Hertz Connection
Ba&
Simply reconfigure the
AC
terminal for the hertz change.
c.
Start
the
engine,
monitor
voltage
and
adjust
engine
no-load
speed.
Adjust
diesel
units
by
the
linkage
between
the
throttle
arm
and
fuel
solenoid
or
the
throttle lever
on
the
injection
pump
..
60 hertz!
no-load
speed,
61.5 - 62.0
hertz.
50 hem!
no-load
speed,
51.5 - 52.0
hertz.
d.
After the
no-load
hertz
adjustment
is
made,
the
no-load
voltage
may
need
to
be
readjusted:
In
most
cases,
if
the
generator
was
producing
the correct
no-load
voltage
at
the
previous
hertz
setting, it
would
be
correct
at
tli.e
changed
hertz
setting.
In
the
event
it
needs
adjustment,
adjust
the
shim
thick-
ness
under
the
laminated
steel
bar of
the
transformer.
60
hertz:
no-load
voltage),
121-124
volt$.
50
hertz:
no-load
voltage,
232~236
volt$.
e.
Load
the
generator
to
the
rated
amperage
output
corresponding
to
the
hertz
speed
of the
generator.
Rated
Loaded
Speed
60
hertz:
loaded
speed,
58.5-
59.0
hertz
50
hertz:
loaded
speed,
·48.5
- 49.0
hertz
The
lowest
acceptable
voltage
at
full
rated
output
(amps)
60
hertz:
108
-
110
volts
50
hertz:
205-210
volts
SIX
STUD
AC
VOLTAGE
CONNECTIONS
115V50Hz
~
@
The
frame
ground
wire
must
lie
moved
when
changing
from
115
volts
and
110/220
volts
50
hertz
to
230
volts
50
hertt;
From
making
con-
nections
to
the
AC;
lermlnal
block,
use
terminal
ends
for
.
1!41nch
studs
that
will
accept
muiH·strand
copper
wire
sized
for
the
amperage
rating
from
the
hot
lead
con-
necl!on.
The
frame
ground
wire
is
whfte
or
white
with
a
·
green
strip.
It
connects
between
the
neutml
stud
and
the
genemtor
fmme.
230V50Hz
·®
®
120V
60HZ
TWELVE
STUD
AC
VOLTAGE
CONNECTIONS
115V50Hz
o=:D
6 g
N
CIRCUIT
l!;!~•dJ
BREAKER
230V50Hz
o=:D
0
.o
6 g
5
~
N
L1
f!Cl
••I
120Y
60Hz.
0 a;::::o
)tJUMPERIS
R_EQUIRED
Engines &
Generator~;
.41
120J240V/60Hz
l1
l2

Other manuals for Westerbeke 12.5 BTDA