10 Installation-general
Note:
Provide a drain & ll valve at the lowest point in the system.
The COB has not been tted with an expansion vessel at the factory. This must be tted
externally (available from the Wolf accessories range). The expansion vessel must be
sized sufciently, in accordance with DIN 4807.
Thereshould not be a shut-offvalvebetween the expansion vessel
andtheoilcondensingboiler,becauseotherwisethepressurebuild-up
wouldpermanentlydamagetheboilerduringheating.Thereisariskof
systemcomponentsrupturing,givingrisetoariskofscalding.
This does not include buttery valves upstream of the expansion vessel. The safety
assembly from the Wolf accessories range includes an integral 3-bar safety valve. Route
the discharge pipe into a drain outlet.
The minimum system pressure is 1.0 bar.
The oil condensing boiler is permitted exclusively for sealed systems of up to 3 bar.
The maximum ow temperature is factory-set to 75°C and may be adjusted to 90°C if
required. In DHW mode, the max. ow temperature is factory-set to 80°C and may be
adjusted to 90°C if required.
It is only possible to refrain from using a minimum flow rate at
temperatureslowerthan80°C,topreventdamagetotheheatexchanger
fromoverheatingandsteamknocking.
Thereturnlinetotheappliancemusthaveadirttrap.Asludgeseparator
withmagnetiteseparatorshouldbeusedtoprotecttheapplianceand
thehighefciencypumpfromdirt/sludgeandmagnetite.
Depositsintheheatexchanger mayleadtoboilingnoise,adropin
performanceorfaultsintheappliance.
Before commissioning,carryout a tightness test on all hydraulic
pipework:
Iftheapplianceisnotwatertight,thereisariskofleaksandresulting
materiallosses.
Testpressureontheheatingwatersidemax.4bar
Priortotesting,closetheshut-offvalvesintheheatingcircuitforthe
appliance,becauseotherwise,thesafetyvalve(accessory)opensat
3bar.Theappliancehasalreadybeentestedatthefactoryfortightness
at4.5bar.
Themaximumowratemustnotexceed6000l/h(100l/min)