EasyManua.ls Logo

Wolf COB - CO Check;Adjustment by Matching the Pipe Lengths

Wolf COB
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
49
3062547_201802
31 CO
2
check/adjustmentbymatching
thepipelengths
CO
2
adjustmentby
matchingthepipelengths
HG 00 CO
2
adjustments
Factory setting: 3
1 2 3 4 5
Lower CO
2
valueHigher CO
2
value
WithcontractorparameterHG00(seechapter19"Contractorlevelparameters"),
theappliancescanbematchedtotheuesystembychangingthespeedfor
bothstagesandthereforetheCO
2
valuecanbechanged.
- Remove front and top casing.
- Remove the cap from the r.h. "ue gas" test port.
- Insert the test probe of the CO
2
measuring instrument into the "ue gas" test port
(approx. 70 mm).
- Turn the program selector switch on the BM module to "Emissions test" .
(Illuminated signal ring as status indicator ashes yellow.)
- Measure the CO
2
content and compare it against the values given in the stage 2 table
below.
- If required, alter the CO
2
content with parameter HG00.
- Modifying the parameter HG00 has also adjusted the speed for stage 1. For
checking purposes, the boiler must be set to stage 1.
- Switch HG28 burner operating mode from 2(two-stage) to 1(single stage).
- Measure the CO
2
content and compare it against the values given in the stage 1
table below.
Appliance open COB-15 COB-20 COB-29 COB-40
Set CO
2
value
Stage 2 12,7 ± 0,3%
Stage 1 12,7 ± 0,3%
O
2
set value
Stage 2 3,8 ± 0,4%
Stage 1 3,8 ± 0,4%
- If the value lies outside of the set value, the CO
2
-value must be set
via the pump pressure (see Commissioning without Wolf control accessories).
- Reset HG28 burner operating mode from 1 to 2.
CO
2
check/settinginthelower
load(stage1)
AdjustingtheCO
2
valueinthe
upperloadrange(stage2)
(emissionstestmode)

Table of Contents

Other manuals for Wolf COB

Related product manuals