31
3062547_201802
23 Contractorlevelparameters
The heating circuit pump is switched OFF during cylinder heating with DHWpriority
(0). The boiler energy will then be used exclusively for DHW heating. The burner shuts
down and the heating circuit pump is started as soon as the cylinder has reached its
set temperature. The cylinder primary pump runs on, in summer operation and at most,
for the period selected under parameter HG19 (cylinder primary pump run-on time).
In winter mode, the cylinder loading pump runs on for a xed time of 2 minutes after
successful cylinder heating.
The heating circuit pump continues to operate in parallelDHWmode(1). Cylinder
heating ends when the cylinder reaches the set water temperature. The cylinder primary
pump runs on, in summer operation and at most, for the period selected under parameter
HG19 (cylinder primary pump run-on time).
InparallelDHWmode(1),theheatingcircuitcantemporarilybeoperated
atahighertemperature.
Parallel operation in conjunction with a stratification cylinder is not
recommended.
Note
DHWparallelmode
ParameterA10
A10
0
Factory setting: 0
Setting range: 0 / 1
Contractorlevel
Press r.h. rotary selector to, in the 2nd to change to the 2nd programming level. Turn
the r.h. rotary selector clockwise to select the contractor level and conrm the selection
by pressing the r.h. rotary selector again.
The display shows the code scan.
Contractor
The correct code is set by pressing (display indication ashes) and then turning the r.h.
rotary selector from0to1. After changing the code from 0 to 1, pressing the r.h. rotary
selector again conrms the setting; you are then at the contractor level.
Codescan
code NO
- - - -
Factory setting: 1
The boiler circuit pump operates constantly if the outside temperature stays below the
selected value. The burner starts and heats the boiler to at least 20 °C if the boiler water
temperature falls below +5 °C.
Thefactorysettingmayonlybechangedifitisguaranteedthatheating
systemanditscomponentswillnotfreezeatlowexternaltemperatures.
Incorrectoperationcanleadtosystemfaults.
PleasenotewhenadjustingparameterA09(frostprotection/outside
temperature),thatfrostprotectionisnolongersafeguardedifyouset
temperatureslowerthan0°C.Thiscanleadtoheatingsystemdamage.
Note
Note
Frostprotectionlimit
ParametersA09
2.0
Factory setting: 2°C
Setting range: -20 to +10 °C
A09