3062547_201802
MaximumDHWtemperature
ParameterA14
65
Factory setting: 65°C
Setting range: 60 to 80 °C
A14
At the factory, the maximum DHW temperature is set to 65°C. This temperature can
be enabled at 80 °C, if for commercial reasons a higher DHW temperature is required.
If pasteurisation has been activated (BM), the DHW cylinder will be heated to the selected
maximum DHW temperature during the rst cylinder heating of the day.
Takeadequatemeasurestopreventscalding.
ParameterHG22(maximumboilerwatertemperature)shouldbesetat
least5KhigherthantheselectedmaximumDHWtemperature.
InconjunctionwiththeTSstraticationcylinder,DHWtemperaturesof
over60°Carenotpermitted,sincethisleadstoacceleratedscalingin
theDHWheatexchanger.
To save energy and protect against scaling if the total hardness is
greaterthan15°dH(2.5mol/m³),theDHWtemperaturemaybesetto
amaximumof50°C.
Ifthetotalhardnessisgreaterthan20°dH(3.58mol/m³),werecommend
usingawatertreatmentfacilityinthecoldwatersupplylineforDHW
heating, to prolong the maintenance interval (descaling DHW heat
exchanger).
Note
23 Contractorlevelparameters
The burner switching differential regulates the burner temperature within a set range
by switching the burner ON and OFF.
The switching differential between burner stage 1 and burner stage 2 is always half the
switching differential.
See also the parameter HG31 diagram.
Burnerswitchingdifferential
ParametersHG01
HG01
10
Factory setting: 10K
Setting range: 5 to 20K
This parameter shifts the minimum and maximum fan speed parallel downwards or
upwards.
This enables the CO
2
value for burner stages 1 and 2 to be adjusted at the same time.
See also the chapter “CO
2
adjustment by matching the pipe lengths"
One unit = 120 r.p.m
Setting 3 = set value, burner control unit
Tubetrimming
ParameterHG00
HG 00
3
Factory setting: 3
Setting range: 1 to 5