EasyManua.ls Logo

Wolf COB - Oil Connection in the Single Line System

Wolf COB
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
22
3062547_201802
16 Oilconnectioninthesingleline
system
Secure the lter vent combination with the integrated shut-off valve and retainer to the
positions provided for this. In doing this, the oil hose should be a max. of 90 cm outside
of the housing during rear wall implementation. The lter vent combinations must be
freely accessible once installed.
Onlyuselterinsertsmadeofsinteredplasticwith25-40μmto
preventcontaminationoftheoilnozzlewithintheserviceinterval.
Contaminatedoilnozzlesleadtotheboilerfailing.
The system must be connected as a single line system. A lter/air vent valve combination
with an integrated shut-off valve from the Wolf product range must be installed.
Oldertwo-linesystemsmustbeconvertedtosinglelinesystems.Two-
linesystemsleadtoacceleratedoilageingandthepenetrationofair
intotheoil.Theyarenolongerinlinewiththelatesttechnology.
Onlymaterialsthataresuitableforoillinesshouldbeused.Inthecase
ofcopperpipes,onlymetalliccompressionttingoliveswithsupport
sleevesarepermissible.Theyareareliablemeansofpreventingairintake.
In accordance with TRÖl, the oil supply shall be checked for its perfect
condition and proper installation and a nal tightness check shall be carried out.
This inspection shall be performed:
Before commissioning
For underground oil lines, before they are covered and
after work on the oil lines (except for oil lter changes)
Inordertopreventdamagetotheoilpump,thefueloilmustbesupplied
tothelterusingasuitablemanualpump.
Thetemperaturemustnotfallbelow+5°C.Externaltanksmusthave
supplementaryheatingfacilities.Theoillinesmustbeinstalledwhile
thesystemisisolatedfromtheelectricalsupplyinordertoavoidleaks.
Contaminantscanleadtosystemdamage.Theoillinemustbeushed
priortocommissioning.
The maximum possible suction line length results from the pressure losses on the
pipes and ttings and the inlet height. All vertical and horizontal pipes are identied as
line lengths.
The following table can be used for sizing. When sizing the line lengths, the lter, non-
return valve and six 90° bend resistances are already taken into account.
Installing suction lines of a max. of 40 m is recommended.
The maximum permitted negative pressure in the suction line is 0.3 bar.
Device
Throughput
Inner line
Ø
Inlet height H (m)
kg/h mm +4 +3 +2 +1 0 -1 -2 -3
COB-15
COB-20
COB-29
Up to 2.5 4 40 40 40 40 40 35 25 13
COB-40 Up to 3.7 4 40 40 40 38 29 22 15 9
Floating or raised suction shall be used, if permitted.
Floating suction is not permitted for underground oil tanks or for oil tanks for which a
special draw-off device is prescribed by the manufacturer.
Oil lines that are too large may lead to operating faults caused by trapped air. The oil
supply must therefore be designed with an interior line diameter of 4 mm.
Oillter/oillineinstallation
Note
Note
Note
Maximumlinelengthsinsingleline
systems
Floating air
extraction
Oil pump,
burner
+
Anti-trap valve
Fig.:
Single line system with pump lower than tank
Fig.:
Single line system with pump higher than tank
Oil pump,
burner
Floating air
extraction
-

Table of Contents

Other manuals for Wolf COB

Related product manuals