EasyManua.ls Logo

Wolf COB - CO Check;Adjustment Via Pump Pressure

Wolf COB
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
52
3062547_201802
33 CO
2
check/adjustmentviapump
pressure
CO
2
settingsvia
pumppressure
If no control accessory is connected to the appliance or the CO
2
set value is
notachievedbymatchingthepipelengths,theCO
2
settingismadeviapump
pressurecontrol:
- Remove front and top casing.
- Pivot the control unit downwards.
- Insert the oil pressure gauge into the pump's pressure gauge test port.
- Remove the cap from the r.h. "ue gas" test port.
- Insert the test probe of the CO
2
measuring instrument into the "ue gas" test port (approx.
70 mm).
- Turn the heating water temperature selector to "Emissions test"
.
(illuminated signal ring as status indicator ashes yellow.)
- Measure the CO
2
content and compare it against the values given in the stage 2
table below.
- If required, amend the CO
2
content with the pressure regulating screw stage 2 with
a 4 mm Allen key (Danfoss design) or SW 8 open-ended spanner (Suntec design).
Turnclockwise-higherCO
2
value
Turnanti-clockwise-lowerCO
2
value
- Check whether the pump pressure is still within the tolerance range.
If not, then check the nozzle and mixer head.
- Terminate the emissions test mode by turning the DHW temperature selector back to
its original position.
AdjustingtheCO
2
valueinthe
upperloadrange(stage2)
(emissionstestmode)
Vacuum
measurement
connection
Vacuum
measurement
connection
Oil pressure
test connection
Oil pressure
test connection
Pressure regulating
screw, stage 2
Pressure regulating
screw, stage 2
Danfoss oil pump
Suntec oil pump
AdjusttheCO
2
valueinthe
lowerload(stage1)
- Press the reset button.
- Set the heating water temperature selector to 8.
- Approx. 2 min. after the burner starts, measure the CO
2
content with the CO
2
test
equipment and compare it against the values given in the stage 1 table below.
- If required, amend the CO
2
content with the pressure regulating screw stage 1 with
a 4 mm Allen key (Danfoss design) or SW 8 open-ended spanner (Suntec design).
Take this measurement within 4 s. of the burner start. If necessary, repeat the start
phase for setting procedures by turning back the heating water temperature selector
and pressing the reset button.
Turnclockwise-higherCO
2
value
Turnanti-clockwise-lowerCO
2
value
Appliance open COB-15 COB-20 COB-29 COB-40
Set CO
2
value
Stage 2 12,7 ± 0,3%
Stage 1 12,7 ± 0,3%
O
2
set value
Stage 2 3,8 ± 0,4%
Stage 1 3,8 ± 0,4%
Appliance open COB-15 COB-20 COB-29 COB-40
Stage 2 Pump pressure 12.0 ± 2.5 bar 16.8 ± 2.5 bar 16.8 ± 2.5 bar 23.5 ± 2.5 bar
Stage 1 Pump pressure 5.0 ± 1.0 bar 8.5 ± 1.0 bar 8.5 ± 1.0 bar 11.0 ± 1.0 bar
Thepumppressureinstage2mustalwaysbegreaterthanthatinstage
1topreventdamagetotheoilpump.
- Check whether the pump pressure is still within the tolerance range. If not, then check
the oil nozzle and mixer head.
- Terminate boiler operation by turning the heating water temperature selector back to
its original position.
- Remove the oil pressure gauge and close the aperture again.
Note
Pressure
regulating
screw
Stage 1
Pressure
regulating
screw
Stage 1
Danfoss oil pump
Suntec oil pump

Table of Contents

Other manuals for Wolf COB

Related product manuals