Discrete inputs --------------------------------------------------------------------------------------- isolated
- Input range (V
Cont, digital input
) ..................................... Rated voltage 12/24 Vdc (6 to 32 Vdc)
- Input resistance ............................................................................................. approx. 6.8 kΩ
Relay outputs --------------------------------------------------------------------------------- potential free
- Contact material ........................................................................................................ AgCdO
- General purpose (GP) (V
Cont, relay output
)
AC .............................................. 2.00 Aac@250 Vac
DC ................................................ 2.00 Adc@24 Vdc
0.36 Adc@125 Vdc
0.18 Adc@250 Vdc
- Pilot duty (PD) (V
Cont, relay output
)
DC ................................................ 1.00 Adc@24 Vdc
0.22 Adc@125 Vdc
0.10 Adc@250 Vdc
Analog inputs (XPD, XPQ) --------------------------------------------------------------- freely scaleable
- Resolution .................................................................................................................... 10 Bit
- 0/4 to 20 mA input ..................................................... Difference measurement, load 150 Ω
- 0 to 5/10 Vdc input .................. Difference measurement, input resistance approx. 16.5 kΩ
- Pt100/Pt1000 input .................................... for measuring resistances according to IEC 751
[Pt100] ............. 2/3-conductor measurement, 0
to 200 °C
[Pt1000] ............. 2-conductor measurement, -30
to 200 °C
- 0 to 180/380 Ω input ................................ difference measurement, sensor current 1.9 mA
Analog outputs (XPD, XPQ) ---------------------------------------------------------------------- isolated
- at rated output ............................................................................................... freely scalable,
- Insulation voltage ................................................................................................. 3,000 Vdc
- Versions ........................................................ 0 to 5 Vdc, +/-5 Vdc, 0 to 10 Vdc, 0 to 20 mA
- Resolution PWM ................................................................. 8/12 Bit (depending on model)
- 0/4 to 20 mA output ............................................................................ maximum load 500 Ω
- 0 to 10 V/+/-5 V output ................................................................. internal resistance 1 kΩ
MPU input --------------------------------------------------------------------------------------------- isolated
- Input impedance .................................................................................... min. approx. 17 kΩ
- Input voltage ............................................................ (see Table 5-15: MPU - input voltage)