Rectifying faults
F0 (and possibly ) flashing.
Internal failure
Check Action
1. B Activate menu option
Show service parameters.
B Select 9.3 GFA-Asic-error.
A message is displayed.
B Record figure displayed in service report.
↓2.
2. B Select 5.2 GFA status / error.
A message is displayed.
B Record figure displayed in service report.
3. B Select Settings -> Service ->
Further options -> Fault history.
Other faults apart from F0 dis-
played?
yes: B Deal with fault(s) displayed as instructed in rele-
vant fault table(s) .
no: ↓3.
4. flashing? yes: B Press button .
B Initiate demand for heat by pressing the . but-
ton and then cancel after 30 seconds by pressing
the button again.
B Initiate demand for heat twice more as described
above.
F0? ↓4.
no: ↓4.
5. The PCB control board is damaged. B Power OFF the appliance.
B Disconnect the boiler electrical connection.
B Change PCB control board.
B Reconnect the boiler electrical connection.
B Turn ON the appliance.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Worcester GREENSTAR HE combi Series and is the answer not in the manual?

Worcester GREENSTAR HE combi Series Specifications

General IconGeneral
BrandWorcester
ModelGREENSTAR HE combi Series
CategoryBoiler
LanguageEnglish

Related product manuals