Adjusting Settings in Configuration Mode
975-0784-01-01 53
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
LBCO Recovery Voltage
04 13.1
10.2 to 16.0
and OFF
The range is from LBCO voltage + 0.2 to 16, adjusted by 0.1
increments. Selecting OFF or a higher value than the battery’s
actual fully-charged voltage level will disable the auto-recovery
feature. You may manually reset the inverter/charger when the low
battery cut off event occurs.
Power Save Time
05 25 OFF, 1 to 25
The range is from 1 to 25, adjusted by 1-h increments. The next
setting after 25 is OFF.
Power Save (Load
Sensing) Mode
06 dIs
ENA (enable),
DIS (disable)
When enabled, the inverter/charger’s “no load loss can be
reduced further when total load is less than 25W.
Output Frequency
07 60
60
50
After changing the output frequency setting, turn the unit off and
then on again, in order for the change to take effect.
Output Voltage
08 120
120
110
108
Inverter Output Power
Limit (Freedom XC
1000)
09 1.0 0.1 to 1.0
The wattage setting value can be adjusted by 100-watt
increments. Use with Inverter Output Power Limit Timer especially
when pairing with a lithium ion battery. 0.1 is equivalent to 100
watts.
Inverter Output Power
Limit (Freedom XC
2000)
09 2.0 0.1 to 2.0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xantrex Freedom XC 2000 and is the answer not in the manual?

Xantrex Freedom XC 2000 Specifications

General IconGeneral
Continuous Power2000W
Surge Power4000W
Input Voltage12V DC
Output Voltage120V AC
Output Frequency60 Hz
WaveformPure Sine Wave
Efficiency90%
Operating Temperature-4°F to 140°F (-20°C to 60°C)
Transfer Time20ms