Adjusting Settings in Configuration Mode
54 Freedom XC Owner's Guide
Setting Name
Setting
Number
Default
Value
Range of
Values
Description
Inverter Output Power
Limit Timer
10 300 1 to 300
When the range is from 1 to 20, the timer setting value can be
adjusted by 1-second increments. When the range is from 20 to
300, the timer setting value can be adjusted by 10-second
increments.
Use with Inverter Output Power especially when pairing with a
lithium ion battery. The timer is automatically disabled if the
maximum Inverter Output Power limit is selected.
Transfer Mode
11 APL
APL(appliance)
UPS (UPS)
Selecting APL- appliance sets the transfer time from line to battery
to 20ms. Selecting UPS (uninterruptible power supply) sets the
transfer time from line to battery to 10ms. NOTE: Do not connect
motor loads when in UPS transfer mode. See Troubleshooting on
page 71.
Utility AC Under Voltage
Level
12 90 85 to 110
Inverter Shutdown
Recovery
13 MAT
At0(auto-
restart)
MAT(manual
restart)
The inverter shuts down when there is an over temperature,
overload, and short circuit condition. Selecting ATO (auto-restart)
will allow the inverter/charger to recover automatically from a
shutdown up to three times maximum. Selecting MAT (manual
restart) allows the user to restart the inverter/charger by performing
a manual reset, that is, by acknowledging the restart via the
display panel.