100
properly.
Re-energize
after eliminating
errors
15
0
E-150
Motor U/V/W
phase break
UVW phase break
during self-inspection
Check power
line U/V/W
connection is
normal
16
0
E-160
Motor output
power overload
Motor output power
over the rated power
1. Change larger
power motor
2. Check the
motor shaft
wiring
1
E-161
The heating
power overload
Motor overheating
1P0-33 confirm
motor code
2. check the
motor shaft
connection
3. change larger
power motor
4
E-164
The bus
capacitor
overload
Power supply not
stable, motor load too
large, cause the bus
capacitor charge
frequently
1. use 3 phase
220V power
supply for 220V
drive
2. change larger
power motor
5
E-165
Prevent from
blocking alarm
When the blocking time
reached P0-74 (S) and
motor speed lower
than(1rpm), current
1. monitor
U0-02 motor
torque, check if
P3-28, P3-29