EasyManua.ls Logo

Xtralis XCC-010 - Auxiliary;GPI and Programming

Xtralis XCC-010
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XCC Product Guide Xtralis Pty Ltd
10 www.xtralis.com
3.4 Auxiliary / GPI Terminals
The Reset (GPI) terminals are used for either Reset, Mains OK or Standby functions (refer to Table 3-2). Note
that Xtralis VSC configuration is required to select the required GPI function. There are two connection
methods available for the GPI input:
l Method 1: Use the Bias terminals which provide 10 VDC supply to initiate the required GPI function
(Figure 3-2).
l Method 2: Use an external power supply (5-24 V). Connect the Reset (+) terminal to the positive out-
put and the Reset (-) terminal to the ground output of the external power supply. Note the voltage input
to Reset (+) and Reset (-) terminals is isolated from the system by an opto-coupler device.
The Bias, Reset (GPI) and LED terminals are located on the termination card (Figure 3-1).
The LED terminals provide a 5V, 15 mA DC supply via an internal 220 ohm resistor to power a remote LED.
Legend Pins
A Switch 1 Bias (-)
B LED 2 Reset (-)
3 Reset (+)
Switch 4 Bias (+)
Disable Close Position 5 LED (+)
Reset Open Position 6 LED (-)
Figure 3-2: Wire connection for Auxiliary/GPI Terminals
Table 3-2: GPIFunctions
Function State Change
Mains OK The detector monitors the state
of the external power supply and
responds to the following
conditions.
Mains OK 5 VDC is at this
terminal.
Mains Fail 2 VDC is at this
terminal.
Standby Mode The detector is Disabled and the
aspirator turns OFF when ≥5
VDC is at this terminal.
No Alarms can be generated in
this state.
Reset /
Disable
While power is applied to the
GPI the detector is disabled. In
addition, the connection of
power to the GPI resets the unit.
5 VDC Detector Disables.
2 VDC Detector Reset.

Related product manuals