EasyManua.ls Logo

Xtralis XCC-010 - Wiring Examples and Power

Xtralis XCC-010
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Xtralis Pty Ltd XCC Product Guide
www.xtralis.com 11
3.5 Programming Socket
The 9 pin programming socket on the termination card provides the communication interface between the
detector and a PC running Xtralis VSC. Connect the PC to the detector using a RS232 data cable directly to
the 9 pin programming socket.
3.6 Typical Wiring to a Fire Panel with an EOL Resistor
The diagram below shows the correct way to wire XCC detectors to a conventional fire alarm control panel
(FACP). It also shows where an End Of Line (EOL) resistor is correctly installed.
Legend Line Impedance
A Fire Relay EOL Quiescent
B Pre-Alarm Relay Short Fire Alarm
C Fault Relay Open Fault
D GPIInput
E Conventional
Loop Input
F Reset Contact
G To next detector
or EOLresistor
Figure 3-3: Typical wiring to a fire panel with EOL resistor
3.7 Wiring to an Addressable Loop Module
This wiring example is for wiring XCC detectors to a typical Input/Output Loop module (3 input 1 output).
These are example drawings. Refer to the appropriate product manual for the exact wiring details of the third
party equipment.
Legend Line Impedance
A Fire Relay EOL Quiescent
B Pre-Alarm Relay Fire Fire Alarm
C Fault Relay Open Wiring Fault
D GPIInput Short Detector Fault
E Fire
F EOL
G Input 1
H Input 2
I Output
(configured on
reset)
Figure 3-4: Typical wiring to an input/output loop module

Related product manuals