XCC Product Guide Xtralis Pty Ltd
28 www.xtralis.com
7.3 Default Settings
Table 7-2: Default values for the XCC detector
Parameter Default
Value
Range Minimum
Access
Minimum Maximum
Fire-Alarm Threshold Level I Level I
(highest
sensitivity,
lowest
threshold)
Level IV
(lowest
sensitivity,
highest
threshold)
Adm
Simultaneous Alarm
Delays
10 Seconds 0 Seconds 60 Seconds Adm
Air flow Thresholds Normal Normal Wide
Faults Latched Latched n/a n/a Adm
Filter Service Interval 1825 days (5
years)
1 day
(Dependent
on
environment)
1825 days (5
years)
Adm
7.4 Spare Parts
On larger sites having multiple detectors it is advisable to stock certain critical spare parts. A list of spare
parts with quantities required is given below:
Table 7-3: Recommended spare parts stock
Part No. Description Number of detectors Installed to warrant ONE
Spare Part
Normal Service Mission Critical
VSP-005 Filter Cartridge 50 20
VSP-501 Aspirator n/a 20