XCC Product Guide Xtralis Pty Ltd
14 www.xtralis.com
4.2 Connection to Pipe Network
4.2.1 Inlet Pipes
To connect the detector to the Pipe Network:
1. Ensure a minimum length of 500 mm (20 in.) of straight pipe before terminating the pipe at the air inlet
port of the detector.
2. Square off and de-burr the end of the sampling air pipe, ensuring the pipe is free from debris.
3. Insert the pipe into the inlet port ensuring a firm fit. DO NOT glue the inlet pipes to the Pipe Inlet Man-
ifold.
4.2.2 Air Exhaust Pipe
Unplug the air exhaust port at the bottom of the detector. If necessary pipe the exhaust back to the protected
area. The maximum suggested length for the exhaust pipe is 4 m (13 ft.).
Note: Refer to and fill in Installation Checklist on page 17.