What does External Fault EF mean on my YASKAWA A1000 Controller?
- EEmily ChavezAug 28, 2025
The YASKAWA Controller External Fault (EF) alarm indicates that a forward and reverse command were input simultaneously for longer than 500 ms, which stops a running motor. You should check the sequence to ensure that the forward and reverse inputs are not set at the same time.