EF2
External fault (input terminal S2)
External fault at multi-function input terminal S2.
EF3
External fault (input terminal S3)
External fault at multi-function input terminal S3.
EF4
External fault (input terminal S4)
External fault at multi-function input terminal S4.
EF5
External fault (input terminal S5)
External fault at multi-function input terminal S5.
Cause Possible Solutions
Minor Fault
Output
(H2-01 = 10)
An external device has tripped
an alarm function.
Remove the cause of the external fault and reset the
multi-function input value.
YES
Wiring is incorrect.
Ensure the signal lines have been connected properly to the
terminals assigned for external fault detection
(H1-oo = 20 to 2F).
Reconnect the signal line.
YES
Multi-function contact inputs
are set incorrectly.
Check if the unused terminals have been set for
H1-
oo
= 20 to 2F (External Fault).
Change the terminal settings.
YES
LED Operator Display Minor Fault Name
oH
Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level.
Cause Possible Solutions
Minor Fault
Output
(H2-01 = 10)
Surrounding temperature is
too high
Check the surrounding temperature.
Improve the air circulation within the enclosure panel.
Install a fan or air conditioner to cool surrounding area.
Remove anything near drive that may cause extra heat.
YES
Internal cooling fan has
stopped.
Replace the cooling
fan. Refer to Cooling Fan Replacement
on page 179.
After replacing the drive, reset the cooling fan maintenance
parameter to (o4-03 = “0”).
YES
Airflow around the drive is
restricted.
Provide proper installation space around the drive as indicated
in the manual. Refer to Correct Installation Orientation on
page 34.
Allow for the specified space and ensure that there is sufficient
circulation around the control panel.
YES
Check for dust or foreign materials clogging cooling fan.
Clear debris caught in the fan that restricts air circulation.
YES
5.5 Alarm Detection
YASKAWA ELECTRIC TOEP C710606 25D YASKAWA AC Drive J1000 Installation & Start-Up Manual
149
5
Troubleshooting

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-JB Series and is the answer not in the manual?

YASKAWA CIMR-JB Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-JB Series
CategoryController
LanguageEnglish

Related product manuals