8.2 Analog Monitor
8-7
8
The monitor factor can also be changed by setting parameters Pn006.2 and Pn007.2.
The analog monitor output voltage is ±8 V (maximum). The output will be limited to ±8 V even if this value is exceeded
in the above calculations.
Parameter Multiplier Remarks
Pn006
Pn007
n.0 ×1 Factory Setting
n.1 ×10 −
n.2 ×100 −
n.3 ×1/10 −
n.4 ×1/100 −
Pn550 Analog Monitor 1 Offset Voltage
Setting Range Setting Unit Factory Setting Setting Validation
-1000.0 to 1000.0
(-1000.0 to 1000.0)
0.1 V 0
(0.0 V)
Immediately
Pn551 Analog Monitor 2 Offset Voltage
Setting Range Setting Unit Factory Setting Setting Validation
-1000.0 to 1000.0
(-1000.0 to 1000.0)
0.1 V 0
(0.0 V)
Immediately
Example
If Pn006 = 0102, Pn422 = 10.00 [%], and Pn550 = 3.00 [V], then
Analog Monitor 1 = Torque reference
= {(-1) × (Torque reference [%]-10%) × 10} + 3[V]
If the torque is 2%,
= {(-1) × (52 [%]-10 [%]) × × 10} + 3 [V]= -7.2 [V] (Analog Monitor 1 output voltage)
1 [V]
100 [%]