2.5 Selecting Peripheral Devices
2-25
2
2.5.2 Molded-case Circuit Breaker and Fuse Capacity
* 1. Nominal value at the rated load. The specified derating is required to select an appropriate
fuse capacity. Refer to 4.4.8 Molded-case Circuit Breaker (MCCB).
* 2. The cutoff characteristics (25°C): 200% two seconds min., 700% 0.01 seconds min.
Note: Do not use a fast-acting fuse. Because the SERVOPACK’s power supply is a capacitor
input type, a fast-acting fuse may blow when the power is turned ON.
The SGDS SERVOPACK does not include a protective grounding circuit. To ensure safety in the system,
install a ground-fault protector against overloads and short-circuit, or a ground fault protector dedicated for
protective grounding combined with the molded-case circuit breaker.
Name Type Specifications
fBattery for Absolute Encoder
Note: No battery is mounted in the battery
case. A battery must be purchased separately.
JUSP-BA01
Battery case
JZSP-BA01
(To mount in the battery case)
ER6VC3N
To connect to a host controller (provided by a
customer)
3.6 V 2000 mAh
,
manufactured by Toshiba Battery Co., Ltd.
Main Circuit
Power Supply
SERVOPACK Model
Power Supply Capacity
per SERVOPACK
(kVA)
Current Capacity of
Breaker or Fuse
(A
rms
)
1
,
2
Capacity
(kW)
SGDS
-
Single-phase
100 V
0.05 A5F 0.25
4
0.10 01F 0.40
0.20 02F 0.60 6
0.40 04F 1.2 12
Single-phase
200 V
0.05 A5A 0.25
40.10 01A 0.40
0.20 02A 0.75
0.40 04A 1.2 8
0.75 08A 2.1 16
Three-phase
200 V
1.0 10A 2.3 7
1.5 15A 3.2 10
2.0 20A 4.3 13
3.0 30A 5.9 17
IMPORTANT