7 Transfer of Parameter Settings
YASKAWA America, Inc. PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide 37
0x0499 L4-01
Speed Agreement
Detection Level
Sets the speed agree detection level or the motor
speed detection level.
0.0~590.0 0.0~400.0
A1-02
Depend
(all 0.0)
0.0
DEC Hz
0x049A L4-02
Speed Agreement
Detection Width
Sets the speed agree detection width or motor
speed detection width.
0.0~20.0 0.0~20.0
A1-02
Depend
2.0
DEC Hz
0x049B L4-03
Speed Agreement
Detection Level(+/-)
Sets the speed agree detection leveler the motor
speed detection level.
-590.0~
590.0
-400.0~
400.0
A1-02
Depend
(all 0.0)
0.0
DEC Hz
0x049C L4-04
Speed Agreement
Detection Width (+/-)
Sets the speed agree detection width or motor
speed detection width.
0.0~20.0 0.0~20.0
A1-02
Depend
2.0
DEC Hz
0x04AE L8-02 Overheat Alarm Level
When the heatsink temperature exceeds the value
set in this parameter, an Overheat Alarm (OH)
will occur. Requires that one of the multi-
function digital output terminals (H2-xx) be set
to 20.
50~150 50~130
kVA
Depend
kVA
Depend
DEC °C
0x04B6 L8-10
Heatsink Cooling Fan
Operation Selection
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only
when the drive is running and for L8-11 seconds
after RUN is removed.
1: Fan always on - Cooling fan operates
whenever the drive is powered up
2: Fan ON in heating of Drive - Fan runs when
drive main circuit overheat is detected
0~2 0~1 0 0
DEC
0x04E1 L8-31
Current Unbalance
Detection Current
Level
Sets the current level to activate Current
Unbalance Protection Detection function with
the drive rated current at 100%.
1~100 0.0~100.0 3 30.0
DEC
0x04EC L8-35
Side-by-Side
Selection
0: Disabled (standard installation).
1: Side-by-Side installation.
2:NEMA 1 Type 1 enclosure
3: Finless / Fin outside
0~3 0~3 0
kVA,
O2-09
Depend
DEC
0x04F1 L8-40
Low Carrier
Frequency Time
Sets the amount of time the drive will operate
with a reduced carrier frequency.
The carrier frequency derating function during
run is disabled when this parameter is set to
0.00 s.
0.00~2.00 0.00~2.00
A1-02
Depend
0.50
DEC sec
0x0471 L8-51
STPo I Detection
Level
Sets the STPo [De-synchronization Error] on the
basis of the output current.
0.0~300.0 0.0~150.0 0.0 0.0
DEC %
0x0589 N3-02
High Slip Braking
Current Limit
Sets the maximum current to be drawn during an
HSB stop. Higher n3-02 settings will shorten
motor stopping times but cause increased motor
current, and therefore increased motor heating.
0~200 100~200
C6-01,
L8-38
Depend
150
DEC %
0x0570 N6-01
Line-to-Line Motor
Resistance Online
Tuning
Tunes the line-to-line motor resistance online.
0: Disabled
1: Enabled (Line-to-line resistance tuning)
2: Enabled (Voltage Adjustm)
In with PG vector control (A1-02 = 3), it is not
possible to enable the resistance online
adjustment only. There is a need to set C3-28=2.
0~2 0~1 0 1
DEC
0x0563 N8-36
Superimposed
Harmonic Frequency
Sets the frequency in Hz for the superimposed
signal used for superimposed harmonics.
200~5000 200~1000 500 500
DEC Hz
Reg.
No.
Param.
No.
Name Description
Setting Range Initial Setting
Base Unit
GA500 V1000 GA500 V1000