6 Control Circuit Wiring
YASKAWA America, Inc. PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide 25
Table 11 Control Circuit Terminal Sizes and Wire Gauge
Model Capacity Terminal Symbol Screw
Tightening
Torque
N•m
(lb-in)
Bare Wire Crimp Ferrule
Recommended
Gauge
mm
2
(AWG)
Wire Range
mm
2
(AWG)
Recommended
Gauge
mm
2
(AWG)
Wire Range
mm
2
(AWG)
V1000
All
capacities
S1-S7, SC, RP,
+V, A1, A2, AC,
HC, H1, P1, P2,
PC, MP, AM,
AC, S+, S-, R+,
R-, IG
M2
0.22 to 0.25
(1.9 to 2.2)
0.75
(18)
Stranded wire:
0.25 to 1.0
(24 to 18)
Solid wire:
0.25 to 1.5
(24 to 16)
0.25 to 0.5
(24 to 20)
0.5
(20)
MA, MB, MC M3
0.5 to 0.6
(4.4 to 5.3)
0.75
(18)
Stranded wire:
0.25 to 1.5
(24 to 16)
Solid wire:
0.25 to 1.5
(24 to 16)
0.25 to 1.0
(24 to 17)
0.5
(20)
GA500
All
capacities
PS, S1 - S7, SN, SC,
SP, AM, AC, A1,
A2, +V, H1, H2,
HC, MP, RP, AC,
D+, D-, P1, C1, P2,
C2
M2
0.22 - 0.25
(1.95 - 2.21)
0.75
(18)
Stranded wire:
0.25 - 1.0
(24 - 17)
Solid wire:
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 0.5
(24 - 20)
MA, MB, MC M3
0.5 - 0.6
(4.4 - 5.3)
0.75
(18)
Stranded wire:
0.25 - 1.5
(24 -16)
Solid wire:
0.25 - 1.5
(24 - 16)
0.5
(20)
0.25 - 1.0
(24 - 17)

Table of Contents