B. Copy Function (Cpy)
The Copy function writes the parameters stored in the digital operator’s EEPROM into the drives non-volatile memory. The
Copy function is possible only for drives of the same type (i.e. from one GPD 315/V7 to another), voltage rating, and con-
trol method (V/f or open loop vector).
5.29 COPY FUNCTION
DIGITAL OPERATOR
DESCRIPTION KEY SEQUENCE
DISPLAY
Table 5-6. Writing Drive Parameters
Set the highest parameter
access level.
This will allow all parameters
to be viewed and set.
Press the key until the LED
is lit on the digital operator.
DSPL
Set Parameter Copy
Access Selection (n177) = 1
Press and hold until n177 is
displayed on the digital operator.
V
Execute upload (Copy)
Using Copy Function
Selection (n176)
PRGM
Then press .
DATA
ENTER
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
PRGM
Use the key to set a “1” in the
display.
V
Then press .
DATA
ENTER
Then press .
DATA
ENTER
Press .
DATA
ENTER
Press three times.
V
Press .
DATA
ENTER
Press the key once.
V
Press the key twice.
V
Press . “CPY” will blink on the
display while writing.
DATA
ENTER

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V7 and is the answer not in the manual?

YASKAWA V7 Specifications

General IconGeneral
ModelV7
CategoryController
ManufacturerYaskawa
Output Frequency0.1 to 400 Hz
TypeAC Drive
Horsepower0.5 to 300 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
Communication InterfacesDeviceNet, Profibus, Ethernet
Operating Temperature-10°C to 50°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Voltage Class200V, 400V
Storage Temperature-20°C to 65°C

Related product manuals