A1-5
PARA- SETTING RANGE SETTING FACTORY USER PARA.
METER NAME (AND UNITS) INCREMENT SETTING SETTING REF.
0: Detection Disabled
1: Detect only at set frequency;
operation continues
2: Detect only at set frequency;
n096 Overtorque Detection (OL3) coast to stop 1 0
3: Detect during all frequency conditions;
operation continues
4: Detect during all frequency conditions;
coast to stop 5.20
Overtorque Detection
n097 Selection (OL3)
0: Detected by output torque
10
(Note 5)
1: Detected by output current
n098
Overtorque Detection
Level (OL3)
30 to 200 1 (%) 160
n099
Overtorque Detection
Delay Time (OL3)
0.1 to 10.0 0.1 (sec) 0.1
n100
Up/Down Hold 0: Disabled
Memory 1: Enabled
10 5.10
n101
Speed Search
Deceleration Time
0.0 to 10.0 0.1 (sec) 2 5.18
n102
Speed Search Operation
Level
0 to 200% 1 (%) 150 5.18
n103
Torque Compensation Gain
0.0 to 2.5 0.1 1.0
(Note 4)
n104
Torque Compensation
5.26
Time Constant
0.0 to 25.5 0.1 (sec) (Note 2)
n105
Torque Compensation 0.1 (W) or
Iron Loss
0.0 to 6550
1 (W)
(Note 1)
n106 Motor Rated Slip (Note 4) 0.0 to 20.0 0.1 (Hz) (Note 1) 2.2, 5.22
n107
Motor Line-to-line
0.001 (ohm)
Resistance
0.000 to 65.50 (Note 1)
n108
Motor Leakage 0.01 (mH)
Inductance (Note 1)
0.00 to 655.0
or 0.1 (mH)
(Note 1)
n109
Torque Compensation
1 (%)
Limit
0 to 250 150 5.26
n110 Motor No-load Current 0 to 99 1 (%) (Note 1) 2.2
n111 Slip Compensation Gain (Note 4) 0.0 to 2.5 0.1 (Note 2)
n112
Slip Compensation Primary
0.0 to 25.5 0.1 (sec) (Note 2)
5.22
Delay Time
n113
Slip Compensation Selection 0: Disabled
10
During Regeneration 1: Enabled
0: Disabled
n115
Stall Prevention Above Base (level is based on setting of n094)
Speed During Run 1: Enabled
10
(level at Fmax is n094 x 0.4)
0: Follows acc/dec #1 (n019, n020)
5.23
or acc/dec #2 (n021, n022)
n116
Stall Prevention During Run,
Note: Multi-Function input selectable 1 0
Accel/Decel Time Select
1: Follows acc/dec #2 (n021, n022)
always
0: Undertorque detection disabled
1: Detected during constant speed running.
Operation continues after detection
n117 Undertorque Detection
2: Detected during constant speed running.
10
Select (UL3)
Operation stops during detection
3: Detected during all frequency conditions.
Operation continues
4: Detected during all frequency conditions.
coast to stop
5.34
0 to 200%
n118
Undertorque Detection Inverter rated current = 100%; if n097 = 0
1(%) 0
Level (UL3) (detection by torque); motor rated torque
becomes 100%
n119
Undertorque Detection
0.1 (sec)
Time (UL3)
0.1 to 10.0 0.1
n120 Frequency Reference 9 (Note 4) 0.00
n121 Frequency Reference 10 (Note 4) 0.01 (Hz) 0.00
n122 Frequency Reference 11 (Note 4) (< 100 Hz) 0.00
n123 Frequency Reference 12 (Note 4) 0.00 to 400.00 or 0.00 5.11
n124 Frequency Reference 13 (Note 4) 0.1 (Hz) 0.00
n125 Frequency Reference 14 (Note 4) (>= 100 Hz) 0.00
n126 Frequency Reference 15 (Note 4) 0.00
n127 Frequency Reference 16 (Note 4) 0.00
Table A1-1. Drive Parameters - Continued