EasyManua.ls Logo

YASKAWA V7

YASKAWA V7
157 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A4-2
•Magnetic contactor
Mount a surge protector on the coil. When using a magnetic contactor to start and stop the drive, do
not exceed one start per hour.
•Ground fault interrupter
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the
current should be 200mA or more and the operating time 0.1 second or more.
•AC and DC reactor
Install a reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to
improve the power factor on the power supply side.
Noise filter
Use a noise filter exclusively for the drive if radio noise generated from the drive causes other
control devices to malfunction.

Table of Contents

Related product manuals