5-32
Continued
E. n057 : Multi-function Output 1 Data 6 or 7 :Overtorque
(terminals MA, MB & MC) Detection
n058 : Multi-function Output 2
(terminals P1 & PC)
n059 : Multi-function Output 3
(terminals P2 & PC)
A Form-C contact, or an open collector output, can be programmed to change states during an
overtorque detection condition.
EXAMPLE OF OVERTORQUE DETECTION
n096 setting: 2 — Overtorque enabled, only at set frequency, coast to stop
n057 setting: 6 — Output contact programmed for overtorque detection
n096 setting: 110 %— Level at which overtorque is sensed
n099 setting: 1.0 s— Time delay before overtorque event occurs
Detection level
(n098 )
Detection
110% time
OUTPUT 100% (n099)
CURRENT/
TORQUE
0
100% Coast
MOTOR stop
SPEED
0
RUN
SIGNAL
FAULT
SIGNAL
CONTACT
OUTPUT
(OVERTORQUE
DETECTION)
TERM. MA & MC)
Overtorque Detection Timing Diagram
5.20 OVERTORQUE DETECTION