YASKAWA VS-606V7 Series - Storing Constants [ENTER Command] (can be written only.)

YASKAWA VS-606V7 Series
223 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
002CH
Inverter status
0 Run 1: Run
1 Zero-speed 1: Zero-speed
2 Frequency agreed 1: Agreed
3 Minor fault (Alarm is indicated)
4 Frequency detection 1 1: Output frequency (n095)
5 Frequency detection 2 1: Output frequency (n095)
6 Inverter operation ready 1: Ready
7 Undervoltage detection 1: Undervoltage detection
8 Baseblock 1: Inverter output baseblock
9
Frequency referecne mode 1: Other than communications
0: Communications
A
RUN command mode 1: Other than communications
0: Communications
B Overtorque detection 1: Detection or overtorque fault
C Undertorque detection 1: Detection or undertorque fault
D Fault retry
E
Fault (Including MEMOBUS communications timeover)
1: Fault
F MEMOBUS communications timeover 1: Timeover
002DH
Multi-function
output
0 MA 1: ON 0: OFF
1 P1 1: ON 0: OFF
2 P2 1: ON 0: OFF
3-F (Not used)
002EH
Inverter
Status
0 Frequency reference loss 1: Frequency reference loss
1-F (Not used)
002FH-
0030H
Reserved
0031H Main circuit DC voltage (1/1 V)
0032H Torque monitor (1/1 % ; 100 %/Motor rated torque ; with sign)
0033H-
0036H
(Not used)
0037H Output Power (1/1 W: with sign)
Register
No.
Bit Description