80
In factory setting, analog voltage of approx. 10 V is output when output
frequency (output current) is 100 %.
Calibrating Frequency Meter or Ammerter (n067)
Used to adjust analog output gain.
Set the analog output voltage at 100 % of output frequency (output cur-
rent). Frequency meter displays 0 to 60 Hz at 0 to 3 V.
Using Analog Output (AM-AC) as a Pulse Train Signal
Output (n065)
Analog output AM-AC can be used as a pulse train output (output fre-
quency monitor, frequency reference monitor).
Set n065 to 1 when using pulse train output.
Constant No. Name Unit Setting
range
Factory setting
n065 Monitor output type - 0, 1 0
FMAM
AC
100 %
10 V
0
Frequency
Meter
Analog monitor gain
can be set by n067.
Analog Output
Output Frequency
(Output Current)
n067
AM
AC
FM
Frequency Meter/Ammeter
(3 V 1 mA Full-scale)
n067 = 1.00
Factory Setting
n067 = 0.30
100 %
10 V3 V
0
Analog Output
Output Frequency
(Output Current)
10 V ×
n067 setting
0.30
= 3 V
Output frequency becomes
100 % at this value.