6. Programming Features
79
Timechart for ACCELERATION/DECELERATION HOLD
Command Input
Note: If a FWD (REV) RUN command is input at the same time as an
ACCELERATION/DECELERATION HOLD command, the motor will
not operate. However, if the Frequency Reference Lower Limit (n034) is
set to a value greater than or equal to the Min. Output Frequency (n016),
the motor will operate at the Frequency Reference Lower Limit (n034).
Using Frequency Meter or Ammeter (n066)
Selects to output either output frequency or output current to analog out-
put terminals AM-AC for monitoring.
Setting Description
0 Output frequency
1 Output current
2 Main circuit DC voltage
3 Torque monitor
4 Output power
5 Output voltage reference
6 Frequency reference monitor
FWD (REV)
RUN Command
ACCELERATION/
DECELERATION
HOLD Command
Frequency
Reference
Output
Frequency
FREQUENCY
AGREE
Signal