6. Programming Features
65
REMOTE Mode
1. Select remote mode.
There are following two methods to select remote mode.
• Select rE (remote mode) for the selection.
• When the local/remote switching function is selected for the
multi-function input selection, turn OFF the input terminal to
select remote mode.
2. Select the operation method by setting constant n003.
n003=0: Enables the Digital Operator (same with local mode).
=1: Enables the multi-function input terminal (see fig. below).
=2: Enables communications (refer to page 109).
=3: Enables communication card (optional).
• Example when using the multi-function input terminal as opera-
tion reference (two-wire sequence)
• For an example of three-wire sequence, refer to page 92.
• For more information on how to select the sequence polarity, refer
to page 191.
Note: When the Inverter is operated without the Digital Operator, always set
constant n010 to 0.
n010 = 0: Detects fault contact of the Digital Operator (Factory setting)
= 1: Not detect fault contact of the Digital Operator
Operating (RUN/STOP Commands) by Communications
Setting constant n003 to 2 in REMOTE mode enables using RUN/
STOP commands via MEMOBUS communications. For commands
using communications, refer to page 109.
Selecting Frequency Reference
Select REMOTE or LOCAL mode in advance. For the method for
selecting the mode, refer to page 63.
FWD RUN/STOP
REV RUN/STOP
n003: 1 (Factory setting: 0)
n050: 1 (Factory setting)
n051: 2 (Factory setting)