142
Press to stop the COPY function.
The following constants are not written if the Inverter capacities differ.
Constants added with software version upgrades will not be written
between VS-606V7 Inverters without the additional constants and VS-
606V7 Inverters with the additional constans.
For this reason, the settings for the additional constants will not be
changed by the copy operation.
Example: Writing Constants from EEPROM in Operator to Inverter
Constant No. Name Constant No. Name
n011 to n017 V/f Settings n108 Motor Leakage Inductance
n036 Motor Rated Current n109 Torque Compensation Volt-
age Limiter
n080 Carrier Frequency Selection n110 Motor No-load Current
n105 Torque Compensation Iron
Loss
n140 Energy-saving Coefficient
K2
n106 Motor Rated Slip n158 Motor Code
n107 Motor Line-to-neutral Resis-
tance
Explanation Operator Display
• Enable the set-
tings for con-
stants n001 to
n179.
• Press to lit
.
• Press to dis-
play the set value.
• Change the set value to 4
by pressing the or
key.
• Press .
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
(Lit for one second.)
↓
(The constant No. is displayed.)
STOP/RESET
DSPL
PRGM
ENTER
ENTER