Typical Setting of the V/f Pattern
Set the V/f pattern according to the application as described below. For
400-V Class Inverters, the voltage values (n012, n015, and n017)
should be doubled. When running at a frequency exceeding 50/60 Hz,
change the Maximum Output Frequency (n011).
Note: Always set the maximum output frequency according to the motor char-
acteristics.
1. For General-purpose Applications
2. For Fans/Pumps
3. For Applications Requiring High Starting Torque
Increasing the voltage of the V/f pattern increases motor torque, but
an excessive increase may cause motor overexcitation, motor over-
heating, or vibration.
Motor Specification: 60 Hz
(Factory setting)
Motor Specification: 50 Hz
Motor Specification: 60 Hz Motor Specification: 50 Hz
10
1.5 30 60 f
50
200
V
10
1.3 25 50 f
50
200
V
Motor Specification: 60 Hz Motor Specification: 50 Hz
18
1.5
360f
24
200
V
18
1.3 2.5
50 f
24
200
V