EasyManua.ls Logo

YASKAWA VS-606V7 Series - Momentary Power Loss Ridethrough Method (n081)

YASKAWA VS-606V7 Series
223 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Programming Features
71
By setting a multi-function input selection (either of n050 to n056) to 11
(acceleration/deceleration time selection 1) or 27 (acceleration/deceler-
ation time selection 2), the acceleration/deceleration time is selected by
ON/OFF combinations of acceleration/deceleration time selection 1 and
acceleration/deceleration time selection 2 (terminals S1 to S7).
The combinations of acceleration/deceleration time selection settings
are shown below.
Accleration/
Deceleration
Time Selection 1
Accleration/
Deceleration
Time Selection 2
Acceleration Time Deceleration Time
OFF OFF Acceleration time 1
(n019)
Deceleration time 1
(n020)
ON OFF Acceleration time 2
(n021)
Deceleration time 2
(n022)
OFF ON Acceleration time 3
(n041)
Deceleration time 3
(n042)
ON ON Acceleration time 4
(n043)
Deceleration time 4
(n044)
No. Name Unit Setting Range Factory
Setting
n019 Acceleration Time 1 Depends on
n018 setting.
(See the next
table.)
Depends on
n018 setting.
(See the next
table.)
10.0 s
n020 Deceleration Time 1 10.0 s
n021 Acceleration Time 2 10.0 s
n022 Deceleration Time 2 10.0 s
n041 Acceleration Time 3 10.0 s
n042 Deceleration Time 3 10.0 s
n043 Acceleration Time 4 10.0 s
n044 Deceleration Time 4 10.0 s

Table of Contents

Related product manuals