98
Factory Settings
• FREQUENCY AGREE Signal (setting=2)
16 Reverse run Closed during reverse run. -
17 Speed search Closed when Inverter conducts a
speed search.
-
18 Data output from com-
munications
Operates multi-function output termi-
nal independently from Inverter opera-
tion
(by MEMOBUS communication)
109
19 PID feedback loss Closed during PID feedback loss 135
20 Frequency reference
loss
Closed during frequency reference loss 151
21 Inverter overheat alert Closed during Inverter overheat alert 91
No. Terminal Factory Setting
n057 MA, MB 0 (fault)
n058 P1 1 (operating)
n059 P2 2 (frequency agree)
Setting Name Description Ref.
Detection Width
±2 Hz
Release Width
±4 Hz
Output Frequency
FREQUENCY AGREE Signal