EasyManuals Logo

YASKAWA VS-606V7 Series User Manual

YASKAWA VS-606V7 Series
223 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #99 background imageLoading...
Page #99 background image
98
Factory Settings
• FREQUENCY AGREE Signal (setting=2)
16 Reverse run Closed during reverse run. -
17 Speed search Closed when Inverter conducts a
speed search.
-
18 Data output from com-
munications
Operates multi-function output termi-
nal independently from Inverter opera-
tion
(by MEMOBUS communication)
109
19 PID feedback loss Closed during PID feedback loss 135
20 Frequency reference
loss
Closed during frequency reference loss 151
21 Inverter overheat alert Closed during Inverter overheat alert 91
No. Terminal Factory Setting
n057 MA, MB 0 (fault)
n058 P1 1 (operating)
n059 P2 2 (frequency agree)
Setting Name Description Ref.
Detection Width
±2 Hz
Release Width
±4 Hz
Output Frequency
FREQUENCY AGREE Signal

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA VS-606V7 Series and is the answer not in the manual?

YASKAWA VS-606V7 Series Specifications

General IconGeneral
BrandYASKAWA
ModelVS-606V7 Series
CategoryInverter
LanguageEnglish

Related product manuals